GE AF-650 GP Programming Manual page 96

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
DN-13 Warning Parameter
Range:
Function:
0
[0 -
View a DeviceNet-specific Warning word. One bit
*
65535]
is assigned to every warning. Please refer to the
DeviceNet Operating Instructions for further
information.
Bit
Meaning
0
not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
Table 3.25
DN-14 Net Reference
Read only from keypad
Option:
Function:
Select the reference source in Instance 21/71 and
20/70.
[0]
Off Enables reference via analog/digital inputs.
*
[1]
On Enables reference via the network.
DN-15 Net Control
Read only from keypad
Option:
Function:
Select the control source in Instance 21/71 and 20/70.
[0]
Off Enables control via analog/digital inputs.
*
[1]
On Enable control via the network.
AF-650 GP Programming Guide
3.11.3 DN-2# COS Filters
Parameters to configure the filtering of Change of State
data.
DN-20 COS Filter 1
Range:
0
[0 - 65535] Enter the value for COS Filter 1 to set up the
*
DN-21 COS Filter 2
Range:
0
[0 - 65535] Enter the value for COS Filter 2, to set up the
*
DN-22 COS Filter 3
Range:
0
[0 - 65535] Enter the value for COS Filter 3, to set up the
*
DN-23 COS Filter 4
Range:
0
[0 - 65535] Enter the value for COS Filter 4 to set up the
*
3.11.4 DN-3# Parameter Access
Parameters to configure the acces to indexed parameters
and defining programming set-up.
DN-30 Array Index
Range:
0
[0 - 255] View array parameters. This parameter is valid only
*
DET-618C
Function:
filter mask for the Status Word. When operating
in COS (Change-Of-State), this function filters
out bits in the Status Word that should not be
sent if they change.
Function:
filter mask for the Main Actual Value. When
operating in COS (Change-Of-State), this
function filters out bits in the Main Actual Value
that should not be sent if they change.
Function:
filter mask for PCD 3. When operating in COS
(Change-Of-State), this function filters out bits in
PCD 3 that should not be sent if they change.
Function:
filter mask for PCD 4. When operating in COS
(Change-Of-State), this function filters out bits in
PCD 4 that should not be sent if they change.
Function:
when a DeviceNet fieldbus is installed.
3
3
95

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents