GE AF-650 GP Programming Manual page 69

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
H-72 Warning Speed Low
Range:
0 RPM
[0 - par.
*
H-73 RPM]
3
3
H-73 Warning Speed High
Range:
par.
[par.
F-17
H-72 -
RPM
par. F-17
*
RPM]
H-74 Warning Reference Low
Range:
-999999.999
*
H-75 Warning Reference High
Range:
999999.999
*
999999.999]
H-76 Warning Feedback Low
Range:
-999999.999
ReferenceFeed-
backUnit
*
68
Function:
Enter the n
value. When the motor
LOW
speed exceeds this limit, the display reads
Speed Low. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01
or 02.
Function:
Enter the n
value. When the motor
HIGH
speed exceeds this limit, the display reads
Speed High. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01 or
02. Program the upper signal limit of the
motor speed, n
, within the normal
HIGH
working range of the frequency converter.
Refer to Illustration 3.31.
Function:
[-999999.999 -
Enter the lower reference limit.
par. H-75]
When the actual reference falls
below this limit, the display
indicates Ref
LOW
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
Function:
[par. H-74 -
Enter the upper reference limit.
When the actual reference
exceeds this limit, the display
reads Ref High. The signal outputs
can be programmed to produce a
status signal on terminal 27 or 29
and on relay output 01 or 02.
Function:
[-999999.999 -
Enter the lower
par. H-77
feedback limit. When the
ReferenceFeed-
feedback falls below this
backUnit]
limit, the display reads
Feedb Low. The signal
outputs can be
programmed to produce
a status signal on
terminal 27 or 29 and
on relay output 01 or
02.
AF-650 GP Programming Guide
H-77 Warning Feedback High
Range:
999999.999
ReferenceFeed-
backUnit
H-78 Missing Motor Phase Function
Option:
[0]
Disabled
*
[1]
Trip 100 ms
[2]
Trip 1000 ms
[3]
Trip 100 ms lim 3
phase detec.
[5]
Motor Check
. The signal
NOTE
This parameter cannot be adjusted while the motor is
running.
3.7.7 H-8# Stop Adjustments
Parameters to configure the special stop features for the
motor and Load Type and Min/Max Inertia.
H-80 Function at Stop
Option:
[0]
Coast
*
[1]
DC hold
[2]
Motor check
[3]
Pre-
magnetizing
DET-618C
[par. H-76 -
999999.999
ReferenceFeed-
*
backUnit]
Function:
Displays an alarm in the event of a
missing motor phase.
No alarm is displayed if a missing
motor phase occurs.
An alarm is displayed if a missing
motor phase occurs.
Function:
Select the frequency converter function
after a stop command or after the speed is
deceled to the settings in H-81 Min Speed
for Function at Stop [RPM].
Leaves motor in free mode. The motor is
disconnected from the frequency converter.
Energizes motor with a DC holding current
(see B-00 DC Hold Current).
Checks if a motor has been connected.
Builds up a magnetic field while the motor
is stopped. This allows the motor to
produce torque quickly at subsequent start
commands (asynchronous motors only). This
Pre-magnetizing function does not help the
very first start command. Two different
Function:
Enter the upper
feedback limit. When
the feedback exceeds
this limit, the display
reads Feedb High. The
signal outputs can be
programmed to produce
a status signal on
terminal 27 or 29 and
on relay output 01 or
02.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents