Parameter Descriptions
F-08 Decel Time 1
Range:
Function:
corresponds to 0.01 s in speed mode. See accel
time in F-07 Accel Time 1.
t dec s x n s RPM
Par
F
.
− 08 =
F-09 Torque Boost
Range:
Function:
100 %
[0 - 300
Enter the % value to compensate voltage in
*
%]
relation to load when the motor is running at
low speed and obtain the optimum U/f
characteristic. The motor size determines the
frequency range within which this parameter
is active.
Motor size
0.25 kW-7.5 kW
Illustration 3.5 Changeover
3.3.2 F-1# Fundamental 1
Parameters to configure drive electronic overload and
high/low speed limits.
F-10 Electronic Overload
Option:
Function:
Thermal motor protection can be
implemented using a range of techniques:
Via a PTC sensor in the motor
windings connected to one of the
analog or digital inputs (F-12 Motor
Thermistor Input). See 3.3.3.1 PTC
Thermistor Connection.
Via a KTY sensor in the motor
winding connected to an analog
AF-650 GP Programming Guide
ref RPM
Change over
<10 Hz
DET-618C
F-10 Electronic Overload
Option:
Function:
input (H-96 KTY Thermistor Input).
See 3.3.3.2 KTY Sensor Connection.
Via calculation of the thermal load,
based on the actual load and time.
The calculated thermal load is
compared with the rated motor
current I
frequency f
Thermal Overload.
Via a mechanical thermal switch
(Klixon type). See 3.3.3.4 Klixon.
For the North American market: The
electronic overload functions provide class
20 motor overload protection in accordance
with NEC.
[0]
No
Continuously overloaded motor, when no
*
protection
warning or trip of the frequency converter is
required.
[1]
Thermistor
Activates a warning when the connected
warning
thermistor or KTY-sensor in the motor reacts
in the event of motor over-temperature.
[2]
Thermistor
Stops (trips) frequency converter when
trip
connected thermistor or KTY sensor in the
motor reacts in the event of motor over-
temperature.
The thermistor cut-out value must be > 3
kΩ.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3]
Elec. OL
Calculates the load when set-up 1 is active
Warning 1
and activates a warning on the display when
the motor is overloaded. Program a warning
signal via one of the digital outputs.
[4]
Elec. OL Trip
Calculates the load when set-up 1 is active
1
and stops (trips) frequency converter when
the motor is overloaded. Program a warning
signal via one of the digital outputs. The
signal appears in the event of a warning
and if the frequency converter trips (thermal
warning).
[5]
Elec. OL
Warning 2
[6]
Elec. OL Trip
2
[7]
Elec. OL
Warning 3
[8]
Elec. OL Trip
3
[9]
Elec. OL
Warning 4
and the rated motor
M,N
. See 3.3.3.3 Electronic
M,N
33