Ec-## Feedback Option - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.14 EC-## Feedback Option

3.14.1 EC-1# Inc. Enc. Interface
EC-10 Signal Type
3
3
Select the incremental type (A/B channel) of the encoder in use.
Find the information on the encoder data sheet.
Select [0] None if the feedback sensor is an absolute encoder
only.
Option:
[0]
[1]
*
[2]
EC-11 Resolution (PPR)
Range:
1024
[10 - 10000] Enter the resolution of the incremental
*
3.14.2 EC-2# Abs. Enc. Interface
EC-20 Protocol Selection
Option:
[0]
None
*
[1]
HIPERFACE
[2]
EnDat
[4]
SSI
EC-21 Resolution (Positions/Rev)
Range:
8192
[4 - 131072] Select the resolution of the absolute
*
EC-24 SSI Data Length
Range:
13
[13 - 25] Set the number of bits for the SSI telegram.
*
106
AF-650 GP Programming Guide
Function:
None
RS422 (5V TTL)
Sinusoidal 1Vpp
Function:
track, i.e. the number of pulses or periods
per revolution.
Function:
NOTE
This parameter cannot be adjusted while
the motor is running.
Select [1] HIPERFACE if the encoder is absolute
only.
Select [0] None if the feedback sensor is an
incremental encoder only.
Function:
encoder, i.e. the number of counts per
revolution.
The value depends on setting in
EC-20 Protocol Selection.
Function:
Choose 13 bits for single-turn encoders and 25
bits for multi-turn encoder.
EC-25 Clock Rate
Range:
260 kHz
[100 - 260
*
kHz]
EC-26 SSI Data Format
Option:
Function:
[0]
Gray code
*
[1]
Binary code Set the data format of the SSI data. Choose
between Gray or Binary format.
EC-34 HIPERFACE Baudrate
Option:
Function:
NOTE
This parameter cannot be adjusted while the
motor is running.
Select the baud rate of the attached encoder.
The parameter is only accessible when
EC-20 Protocol Selection is set to [1] HIPERFACE.
[0]
600
[1]
1200
[2]
2400
[3]
4800
[4]
9600
*
[5]
19200
[6]
38400
3.14.3 EC-6# Monitoring and App.
EC-60 Feedback Direction
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to
the encoder.
[0]
Clockwise
*
[1]
Counter
clockwise
EC-61 Feedback Signal Monitoring
Select which reaction the frequency converter should take in
case a faulty encoder signal is detected.
The encoder function in EC-61 Feedback Signal Monitoring is an
electrical check of the hardware circuit in the encoder system.
Option:
[0]
Disabled
[1]
Warning
*
[2]
Trip
DET-618C
Function:
Set the SSI clock rate. With long
encoder cables the clock rate must
be reduced.
Function:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents