Parameter Descriptions
O-43 PCD Read Configuration
Range:
[1250]
External Reference
[1251]
Pulse Reference
[1252]
Feedback[Unit]
[1253]
Digi Pot Reference
[1257]
Feedback [RPM]
[1260]
Digital Input
[1261]
Terminal 53 Switch Setting
[1262]
Analog Input 53
[1263]
Terminal 54 Switch Setting
[1264]
Analog Input 54
[1265]
Analog Output 42 [mA]
[1266]
Digital Output [bin]
[1267]
Freq. Input #29 [Hz]
[1268]
Freq. Input #33 [Hz]
[1269]
Pulse Output #27 [Hz]
[1270]
Pulse Output #29 [Hz]
[1271]
Relay Output [bin]
[1272]
Counter A
[1273]
Counter B
[1274]
Prec. Stop Counter
[1275]
Analog In X30/11
[1276]
Analog In X30/12
[1277]
Analog Out X30/8 [mA]
[1284]
Comm. Option STW
[1285]
Drive Port CTW 1
[1287]
Bus Readout Alarm/Warning
[1290]
Alarm Word
[1291]
Alarm Word 2
[1292]
Warning Word
[1293]
Warning Word 2
[1294]
Ext. Status Word
[1500]
Operating hours
[1501]
Running Hours
[1502]
kWh Counter
3.10.5 O-5# Digital/Bus
Parameters to configure the control word Digital/Bus
merging.
O-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the network.
[0]
Digital
Activates Coast command via a digital input.
input
[1]
Bus
Activates Coast command via the serial
communication port or network option
module.
[2]
Logic AND
Activates Coast command via the network/
serial communication port, AND additionally
via one of the digital inputs.
AF-650 GP Programming Guide
O-50 Coasting Select
Function:
Option:
[3]
Logic OR
*
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the network.
Option:
[0]
[1]
[2]
[3]
*
O-52 DC Brake Select
Option:
[0]
Digital
*
input
[1]
Bus
[2]
Logic AND ActivatesDC Brake command via the network/
[3]
Logic OR
O-53 Start Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND Activates Start command via the network/serial
[3]
Logic OR
*
DET-618C
Function:
Activates Coast command via the network/
serial communication port OR via one of the
digital inputs.
Function:
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available
when P-20 Motor Construction is set to [1]
PM non-salient SPM.
ActivatesDC Brake command via a digital input.
ActivatesDC Brake command via the serial
communication port or network option module.
serial communication port, AND additionally via
one of the digital inputs.
ActivatesDC Brake command via the network/
serial communication port OR via one of the
digital inputs.
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the network.
Activates Start command via a digital input.
Activates Start command via the serial
communication port or network option
module.
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the network/serial
communication port OR via one of the digital
inputs.
3
3
91