Installing the IAC-D

3.3.2 Standalone IAC-D Installation

Use this procedure to install a separately located IAC-D (see Figure 3-7 and Figure 3-8).
1. Verify that the UPS is properly installed and secured. Refer to the applicable
2. Roll the IAC-D to the installation area.
3. If not already open, unfasten the front door latch and swing the door open.
4. If not already removed, remove the door. Remove the retaining screws located
5. If permanently mounting the IAC-D, proceed to Step 8; otherwise, proceed to
3-10
EATON Powerware

Figure 3-7. 80 kVA UPS with Standalone IAC-D

Powerware 9390 Installation and Operation manual, listed in paragraph 1.5, for
installation instructions.
inside the door at the top and bottom hinge pivot points, then lift the door off.
Save the retaining screws for reinstallation of the door.
Step 6.
9390 IAC-D Installation and Operation Manual S 164201591 Rev B powerware.com
®