Advertisement

AC INPUT
TO UPS
E1, E2, E3
K1
BATTERY
CONVERTER
E4. E5
Powerware 9390 UPS CABINET
SERIAL NUMBER SEVENTH
DIGIT AT "A" OR "B"
OPTIONAL FACTORY-SUPPLIED FOR
LINE--UP–AND–MATCH INSTALLATIONS
OPTIONS
120/100, 120/120 kVA,160/100, 160/120, AND 160/160 kVA
208V INPUT AND 208/120V OUTPUT
WITH UPS SERIAL NUMBER SEVENTH DIGIT AT "A" OR" B"
NOTE:
Move bypass contactor wires to bypass
terminals for dual-feed.
EATON Powerware
9390 IAC-D Installation and Operation Manual S 164201591 Rev B powerware.com
®
E6, E7,
(SEE NOTE FOR
E8, E12
DUAL-FEED)
K5
RECTIFIER
E9, E10,
E11, E12
INVERTER
K3
DISTRIBUTION PANEL OUTPUT
DESCRIPTION:
DRAWING NO:
REVISION:
Powerware 9390 IAC-D
A
E57, E58,
E59, E4
225A
PANELBOARD
NUMBER 2
OUTPUT TO
CRITICAL
LOAD
B
AVAILABLE WITH OPTIONS FOR ONE OR TWO
42-POLE 225A DISTRIBUTION PANELS.
IAC-D ONELINE DRAWINGS
164201591---4
B
Installation Information
225A
PANELBOARD
NUMBER 1
OUTPUT TO
CRITICAL
LOAD
B
SHEET:
2 of 9
DATE:
061506
A-7