Figure 3-5. 80 Kva Ups To Iac-D Joining Brackets - Eaton Powerware 9390 IAC-D Installation And Operation Manual

Integrated accessory cabinet
Table of Contents

Advertisement

Installing the IAC-D
Bracket from Kit
25. Locate the large angle bracket, M4 screws, and large nut from the field kit. Place
26. Align the holes in the other end of the bracket with the holes in the bottom
27. Secure the large nut on the IAC-D hinge.
28. Proceed to paragraph 3.3.3.
29. Remove the right-hand screw from the top right-hand door hinge of the UPS
3-8
EATON Powerware
M4 Screw and
Four Washers
from Kit
UPS
Bracket
from Kit
Top View with Small Bracket
UPS
M4 Screws
from Kit
Front View with Large

Figure 3-5. 80 kVA UPS to IAC-D Joining Brackets

one end of the bracket over the bolt on the bottom side of the lower hinge on the
IAC-D, and loosely secure the bracket to the hinge with the large nut (see
Figure 3-5).
right-hand side of the UPS (see Figure 3-5). Secure the bracket with M4 screws
from the field kit.
cabinet and the left-hand screw from the top left door hinge of the IAC-D.
9390 IAC-D Installation and Operation Manual S 164201591 Rev B powerware.com
®
Existing
Screw
IAC-D
IAC-D
Angle Bracket
Existing Hinge
Nut from Kit