Description, device design, dimension drawing

2.4 Operating displays and signaling

2.4
Operating displays and signaling
Operating display
Signaling contact
Signaling
LED green (5.1) off
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Green LED (5.1) lit
Signaling contact (3), contacts 13-14 closed
Green LED (5.1) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Yellow LED (5.2) lit
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Green LED (5.1) lit and red LED (5.3) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Red LED (5.3) lit
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Red LED (5.3) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
14
6EP1536-3AA00 (24 V/20 A)
LED green, lit for "24 V O. K."
LED flashing green: During the wait time for a delayed start with selector switch C in the "ON"
position
Yellow LED lit for overload condition (U
Red LED lit for latching shutdown as a result of overload (only for selector switch B in the "ON"
position)
LED red flashing for prewarning and latching shutdown as a result of overtemperature
Relay contact (NO contact, contact rating (isolated): 30 V AC/0.5 A, DC 60 V/0.3 A, DC 30 V/1 A)
for "24 V O. K."
< 20 V ± 0.5 V)
out
6EP1536-3AA00 (24 V/20 A)
No supply voltage
Normal operation, output voltage > 20 V ± 0.5 V
Output voltage = 0 V during delayed start
Overload (U
< 20 V ± 0.5 V)
out
Prewarning due to overtemperature, device switches off
after approx. 10 s and latches in this condition. (reset possi-
ble after approx. 3 min with power OFF/ON)
Latching shutdown due to overload
Shutdown due to overtemperature → reset using power
OFF/ON after approx. 3 min
Manual, 05.2018, C98130-A7601-A1-5-7629