Operating mode

The selection is made using individual DIP switches (when supplied, these are in the 0
position).
It is only permissible to connect two identical devices in parallel to increase the power rating
when the output characteristic is switched over using selector switch PO
DIP switch
6EP3434-7SB00-3AX0 (24 V/10 A)
6EP3436-7SB00-3AX0 (24 V/20 A)
COM ⑨:
Selector switch to toggle between the U
0: Display of the output voltage status
1: Internal device parameters are transferred via signaling contact (13, 14) (diagnostics interface)
NOTICE: It is not permissible that the signaling contact is connected on the primary side!
Contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A
HV ⑩:
Setting, about which value, LED "O.K." is lit.
0: > 20 V
1: > 23 V
PO ⑪:
Switching over the output characteristic
0: Constant output voltage "standalone operation"
1: Load-dependent output voltage "parallel operation"
Additional information can be found in the documents:
● Diagnostics interface (https://support.industry.siemens.com/cs/ww/en/view/109763467)
● Faceplates and communication blocks
(https://support.industry.siemens.com/cs/ww/en/view/109760217)
SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
Description, device design, dimension drawing
status display and the communication
out
2.5 Operating mode
to 1:
15