Control Variable - Emerson Tescom ER5000 Series User Manual

Table of Contents

Advertisement

ER5000 —
Internal Variables
70
ID_PROFILE_STATE
This is the run state of the profile.
0 => STOP
1 => START
2 => RUN
71
ID_PROFILE_STEP
This is the step in the profile which is currently being run.
119 ID_UI_PROFILE_STARTRUN
This is the restarting mode of the profile.
0 => Restart profile at the beginning
1 => Resume profile at current profile step
ER5000 Single "Puff" Solenoid Control Variable
73
ID_PULSE
This variable allows opening the inlet or exhaust for the
specified duration for one pulse period. After one pulse
duration, the variable is returned to a value of 0.
0x08fa => Inlet full open
0x0800 => Both valves closed
0x0706 => Exhaust full open
ER5000 Pulse Mode Variables
81
ID_PULSE_PERIOD
This controls the rate of the pulse while pulse mode is active.
The value represents how many passes through the control
algorithm (25 ms per pass) before sending a pulse to one of
the solenoids.
82
ID_PULSE_WIDTH
This controls how long the solenoid is held open while pulse
mode is active. Part of this number compensates for allowed
system fluctuations (or noise) so too small a number will not
open the solenoid valve.
83
ID_PULSE_DEADBAND
This is the error from the setpoint allowed for the pulse
function to stop pulsing. This value is in counts read up
from the sensor. One count of error is .03% and typically this
number is in the range of 0–3.
84
ID_PULSE_ENABLE
This turns the pulse function ON(1) or OFF(0).
231