ER5000 Series —
Features and Specifications
Hazardous Location Model (ER5050) Specifications
USB Communication Interface
USB:
2.0
Maximum cable length:
15 ft / 4.5 m
Connector:
Mini-B
NOTE
NOTE
Due to varying hazardous location wiring requirements, a USB
cable is not included with the ER5050.
CAUTION
CAUTION
RS485 Communication Interface
WARNING
WARNING
Networking:
Up to 32 controllers on one network
Maximum cable length:
4000 ft / 1219 m
Baud rate:
9600
Flow Rate
C v :
0.01
NOTE
NOTE
The flow rate can be increased using a booster regulator.
CAUTION
CAUTION
Accuracy
Room temp:
0.1% of span maximum
WARNING
WARNING
Response Time
Rise Time:
257ms — 10 psig to 90 psig / 0.7 bar to 6.2 bar
Fall Time:
552ms — 90 psig to 10 psig / 6.2 bar to 0.7 bar
NOTE
NOTE
Step response into dead-end system (1 cubic inch volume).
CAUTION
CAUTION
WARNING
WARNING
(cont.)
External Analog Input Impedance
4–20 mA:
250Ω
1–5V:
220KΩ — single input pin to ground
1.7MΩ — differential input
0–10V:
100KΩ
Digital Inputs
Voltage Range/Input Impedance:
4–20 mA:
250Ω
1–5V:
220KΩ — single input pin to ground
1.7MΩ — differential input
0–10V:
100KΩ
Digital Outputs
Current:
50 mA continuous, 100 mA instantaneous
Voltage:
5V to 28V
Type:
Open collector, grounded emitter
Analog Output
4–20 mA:
Better than 0.5% accuracy;
loads from 50Ω to 1000Ω
0–10V DC:
Better than 0.5% accuracy;
loads no less than 5000Ω
23