ER5000 —
The ERTune™ Program: Basic Features
ER Node
This entry field allows you to change the Node Address of
the ER5000.
To change the Node Address of the ER5000
Address
1. Enter a new value in the
NOTE
NOTE
The maximum value that can be used for a Node Address
is 250. Any value higher than 250 that is entered in this field will be
CAUTION
CAUTION
truncated to the first two digits.
WARNING
WARNING
2. The Comm Error Window opens and the ER5000 scans
through the Node Addresses until it reaches the new address
you have entered. The window then closes and the new node
address is registered.
NOTE
NOTE
The Serial Number of the ER Series controller cannot be
changed from the Configure tab.
CAUTION
CAUTION
NOTE
NOTE
The Version Number refers to the current version of the
WARNING
WARNING
ER5000 internal software. It cannot be changed.
CAUTION
CAUTION
WARNING
WARNING
entry field and press the Tab key.
Calibration
These entry fields allow for fine adjustment of the ER5000.
The defaults meet the needs of most applications. However,
your application may require an adjustment of these values to
compensate for external transducers which require calibration,
such as a transducer that has been over pressurized.
To change the calibration of the ER5000
1. Enter a new value in the
press the Tab key.
Zero %
Span %
and/or
entry fields and
180