4.2.4. 1-6* Load Dependent setting
Parameters for adjusting the load dependent motor settings.
1-60 Low Speed Load Compensation
Range:
100 %
1-61 High Speed Load Compensation
Range:
100 %
1-62 Slip Compensation
Range:
100 %
Function:
Use this parameter to gain optimum U/f characteristic when
running at low speed.
*
[0-199 %]
Enter percentage in relation to load when motor runs at low
speed.
Change-over point is automatically calculated based on motor
size.
Function:
Use this parameter to obtain optimum load compensation when
running at high speed.
*
[0 - 199 %]
Enter percentage to compensate in relation to load when motor
runs at high speed.
Change-over point is automatically calculated based on motor
size.
Function:
*
[-400 - 399 %]
Compensation for load dependent motor slip.
Slip compensation is calculated automatically based on rated
motor speed, n
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
4. Parameter Descriptions
.
M,N
NB!
This function is only active when par. 1-00,
figuration Mode
Speed Open Loop
, is set to
and when par. 1-01,
Motor Control Principle
VVC+
to
[1].
4
Con-
[0],
, is set
23