8-06 Reset Control Word Timeout
Option:
*
[0]
[1]

4.9.3. 8-3* FC Port Settings

Parameters for configuring the FC Port.

4.9.4. 8-30 Protocol

8-30 Protocol
Option:
*
[0]
[2]
8-31 Address
Range:
*
1
8-32 FC Port Baud Rate
Option:
[0]
[1]
*
[2]
Select Set-up 1
Change to Set-up 1 upon reestablishment of communication
following a control word timeout.
Select Set-up 2
Change to Set-up 2 upon reestablishment of communication
following a control word timeout.
Function:
Resetting the control word timeout will remove any timeout
function.
No Function
Control word timeout is not reset.
Do Reset
Control word timeout is reset, and parameter goes into
Function
Function:
Select the protocol to be used. Note that changing protocol will
not be effective until after powering off the frequency converter.
FC
Modbus
Function:
Select the address for the bus.
[1 - 126]
FC -bus range is 1-126.
Modbus range is 1-247.
Function:
Select baud rate for FC Port.
2400 Baud
4800 Baud
9600 Baud
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
state.
NB!
Changing baud rate will be effective after re-
sponding to any ongoing bus-requests.
4. Parameter Descriptions
No
4
53