VLT Micro Drive FC 51
14-22 Operation Mode
Option:
*
[0]
[2]
4.11.5. 14-4* Energy Optimizing
These parameters are for adjusting the energy optimization level in both Variable Torque (VT)
and Automatic Energy Optimization (AEO) modes.
14-41 AEO Minimum Magnetization
Range:
*
66%
Function:
Use this parameter for specifying normal operation or to initial-
ize all parameters, except par. 15-03, 15-04 and 15-05.
Normal Operation
Frequency converter runs normal operation.
Initialization
Resets all parameters to default settings, except for 15-03,
15-04 and 15-05. Frequency converter resets during next pow-
er-up.
Par. 14-22 also reverts to default setting
Function:
[40 - 75%]
Enter the minimum allowable magnetization for AEO. Selecting
a low value reduces energy loss in the motor, but may also re-
duce resistance to sudden load changes.
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
4. Parameter Descriptions
Normal Operation
[0].
4
67