VLT Micro Drive FC 51
6-10 Terminal 53 Low Voltage
Range:
0.07 V
6-11 Terminal 53 High Voltage
Range:
10.0 V
6-12 Terminal 53 Low Current
Range:
0.14
*
mA
6-13 Terminal 53 High Current
Range:
20.00
*
mA
Function:
This scaling value should correspond to minimum reference val-
ue set in par. 6-14. See also section
*
[0.00 - 9.90 V]
Enter low voltage value.
Function:
This scaling value should correspond to maximum reference
value set in par. 6-15.
*
[0.10 - 10.00 V]
Enter high voltage value.
Function:
This reference signal should correspond to minimum reference
value set in par. 3-02.
[0.00 - 19.90 mA]
Enter low current value.
The value must be set to min. 2 mA in order to activate the Live Zero Timeout
function in par. 6-01.
Function:
This reference signal should correspond to the maximum refer-
ence value set in par. 6-15.
[0.10 - 20.00 mA]
Enter high current value.