4. Parameter Descriptions

4.12. Parameter Group 15: Drive Information

4.12.1. 15-** Drive Information
Parameter group containing information on operating data, hardware configuration, software ver-
sion, etc.

4.12.2. 15-0* Operating Data

4
Parameter group containing operating data e.g. Operating Hours, kWh counters, Power Ups, etc.

4.12.3. 15-00 Operating Time

15-00 Operating Time
Range:
0 days

15-01 Running Hours

Range:
*
0
15-02 kWh Counter
Range:
0
15-03 Power Ups
Range:
0
15-04 Over Temps
Range:
0
15-05 Over Volts
Range:
*
0
68
Function:
*
[0 - 65535 days]
View running hours of frequency converter.
The value is saved at power off and cannot be reset.
Function:
[0 - 2147483647]
View running hours of motor.
The value is saved at power off and can be reset in par. 15-07,
Reset Running Hours Counter
Function:
[0 - 65535]
View power consumption in kWh as a mean value over one hour.
Reset counter in par. 15-06,
Function:
[0 - 2147483647]
View number of times frequency converter has been powered
up.
Counter cannot be reset.
Function:
[0 - 65535]
View number of times frequency converter has tripped due to
over temperature.
Counter cannot be reset.
Function:
[0 - 65535]
View number of times frequency converter has tripped due to
over voltage.
MG.02.C2.02 - VLT
.
Reset kWh Counter
®
is a registered Danfoss trademark
VLT Micro Drive FC 51
.