4. Parameter Descriptions

4.11.4. Trip Reset, 14-2*

Parameters for configuring auto reset handling, special trip handling and control card self test or
initialisation.
14-20 Reset Mode
Option:
4
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]

14-21 Automatic Restart Time

Range:
10 s
66
*
Manual Reset
AutoReset 1
AutoReset 2
AutoReset 3
AutoReset 4
AutoReset 5
AutoReset 6
AutoReset 7
AutoReset 8
AutoReset 9
AutoReset 10
AutoReset 15
AutoReset 20
Infinite auto reset
*
[0 - 600 s]
MG.02.C2.02 - VLT
Function:
Select reset function after tripping. Once reset, frequency con-
verter can be restarted.
Perform reset via [reset]-button or digital inputs.
Performs one automatic reset after tripping.
Performs two automatic resets after tripping.
Performs three automatic resets after tripping.
Performs four automatic resets after tripping.
Performs five automatic resets after tripping.
Performs six automatic resets after tripping.
Performs seven automatic resets after tripping.
Performs eight automatic resets after tripping.
Performs nine automatic resets after tripping.
Performs ten automatic resets after tripping.
Performs fifteen automatic resets after tripping.
Performs twenty automatic resets after tripping.
Performs an infinite number of automatic resets after tripping.
Motor may start without warning.
Function:
Enter time interval from trip to start of automatic reset function.
This parameter is active when par. 14-20,
Automatic Reset
[0] - [13].
®
is a registered Danfoss trademark
VLT Micro Drive FC 51
Reset Mode
, is set to