Intermediate Positions (Pivot Points); Intermediate Positions (Pivot Points): Define; Signal Behaviour Of Intermediate Positions: Set; Tions 8.2. Intermediate Positions (Pivot Points) - AUMA ACVExC 01.2 Series Operation And Setting Manual

Actuator controls
Hide thumbs Also See for ACVExC 01.2 Series:
Table of Contents

Advertisement

Application functions
Information
8.2.

Intermediate positions (pivot points)

Conditions
Characteristics
8.2.1.

Intermediate positions (pivot points): define

Information
8.2.2.

Signal behaviour of intermediate positions: set

48
If the current speed is lower than the target speed, the speed is increased to the
target speed!
Customer settings M0041
Speed functions M1699
Speed red. range M1906
Speed red. end pos. M1904
Default value: 5.0 %
Setting range: 0.0 ... 25.0 % (in % before reaching the end position, in relation to
the full travel)
Set target speed before reaching end position
The actuator runs to the end position at the target speed set by means of this
parameter.
Customer settings M0041
Speed functions M1699
Speed red. range M1906
Target speed for red. M1905
Default values: 8 (rpm)
Setting range: 6 ... 240 rpm (revolutions/minute)
The adjustable speed range is indicated on the actuator name plate.
The actuator is equipped with a position transmitter.
With the actuator controls, up to 8 intermediate positions (pivot points) can be
set to any value between 0 % and 100 % of the travel.
Each intermediate position can be activated or deactivated individually.
When reaching an intermediate position, a signal can be generated.
A hysteresis can be defined for each pivot point.
Each intermediate position can be set to a value between 0 and 100 % of the travel.
Customer settings M0041
Intermediate positions M0143
Pivot points M0160
Pivot point 1 M0249
Default values: 0.0 % for all 8 intermediate positions
Setting range: 0.0 % (CLOSED) to 100.0 % (OPEN) of the travel
The pivot points also apply to the <Operation profile> function.
Reaching a pivot point (intermediate position) can be signalled:
via indication lights (LEDs) of the local controls or
via output contacts
Each pivot point (intermediate position) can be assigned a specific signal behaviour.
Customer settings M041
Intermediate positions M0143
Signal behaviour M0266
Signal behaviour 1 M0269
Default value: No signal