Actuator controls
ACV 01.2/ACVExC 01.2
3.

Operation

3.1.

Local actuator operation

Information
3.2.

Actuator operation from remote

Local actuator operation is performed using the local controls push buttons of actuator
controls.
Figure 4: Local controls
[1]
Push button for operation command in direction OPEN
[2]
Push button STOP
[3]
Push button for operation command in direction CLOSE
[4]
Push button RESET
[5]
Selector switch
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
Check surface temperature and wear protective gloves, if required.
Set selector switch [5] to position Local control (LOCAL).
The actuator can now be operated using the push buttons [1 – 3]:
-
Run actuator in direction OPEN: Press push button [1]
-
Stop actuator: Press push button STOP [2].
-
Run actuator in direction CLOSE: Press push button [3]
The OPEN and CLOSE operation commands can be given either in push-to-run or
in self-retaining operation mode. For further information, please refer to <Push-to-
run operation or self-retaining local> chapter.
Risk of immediate actuator operation when switching on!
Risk of personal injuries or damage to the valve
If the actuator starts unexpectedly: Immediately turn selector switch to position
0 (OFF).
Check input signals and functions.