Operating Times: Display; Device Temperatures: Display; Oscillation/Vibration Indication - AUMA ACVExC 01.2 Series Operation And Setting Manual

Actuator controls
Hide thumbs Also See for ACVExC 01.2 Series:
Table of Contents

Advertisement

Plant Asset Management
14.6.

Operating times: display

Characteristics
Application
Operating time CLOSE
Operating time OPEN
14.7.

Device temperatures: display

Temp. controls
Temp. control unit
14.8.

Oscillation/vibration indication

Condition
Information
Total accel. in g
Example
120
Maintenance interval M1233
Default value: 10 years
Setting range: 1 month... 10 years
The actuator controls automatically determine the operating time for an operation
between two end positions. For both directions (from OPEN to CLOSE and from
CLOSE to OPEN), the last determined value is saved within a parameter.
Operating time measurement indicated how an actuator installed in plant or a
combination of actuator/gearbox/valve behave with regard to inertia without performing
an operation and measuring the time manually.
Display measured operating times
Asset Management M1231
Operating time M1232
Operating time CLOSE M1234
Operating time OPEN M1235
Indications:
Indicates the measured operating time for the last operation in direction CLOSE
Indicates the measured operating time for the last operation in direction OPEN
Required user level: Specialist (4) or higher.
Asset Management M1231
Device temperatures M0524
Indications:
Indication of current temperature in controls housing
Indication of current temperature in control unit of the actuator (actuator housing)
Electronic control unit with MWG in the actuator (non-intrusive version)
The measured and indicated acceleration matches that the sensor installed within
the control unit at the MWG and not that of the vibration induced at the valve attach-
ment.
Required user level: Specialist (4) or higher.
Asset Management M1231
Oscillation M0960
Total accel. in g M0961
Indication:
Indication of the total acceleration within the actuator controls housing of 0.000 ...
4.000 g.
Configuration of analogue output
The acceleration value can be sent to an analogue output.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Use output AOUT 2 for Total accel. in % signal:
Parameter: Signal AOUT 2 M0132
Actuator controls