Diagnostic Process Controller; Diagnostic Fo Cable; Simulation (Inspection And Test Function); 13.11.1. Actuator Signals - AUMA ACVExC 01.2 Series Operation And Setting Manual

Actuator controls
Hide thumbs Also See for ACVExC 01.2 Series:
Table of Contents

Advertisement

Diagnostics
13.9.

Diagnostic Process controller

13.10.

Diagnostic FO cable

13.11.

Simulation (inspection and test function)

13.11.1. Actuator signals

End position OPEN
End position CLOSED
Torque fault OPEN
Torque fault CLOSE
Thermal fault
108
The following states can be checked via diagnostics:
Parameters
Menu ID
On time
M0594
No. mot. starts/h
M0595
Required user level: Specialist (4) or higher.
Diagnostic M0022
Process controller M0883
Menu M0883 is only visible if function Process controller M0741 is activated.
The following states can be checked via diagnostic:
Parameters
Menu ID
Process setpoint
M0884
Actual process value
M0885
Op. com. PID contr.
M0886
Menu is only visible if on time monitoring (parameter Duty type monitoring M0573)
is activated.
Required user level: Observer (1) or higher.
Diagnostic M0022
FO cables M0638
The following states can be checked via diagnostic:
Parameters
Menu ID
FOC level channel 1
M0639
DIN 4 configuration
M0640
FOC RS-485 error
M0762
FO cable baud rate
M0641
FOC FPGA version
M0711
The service personnel or the commissioning engineer can use this simulation function
to simulate the operation and failure behaviour of the actuator or the actuator controls
to check the interface to the DCS and the correct behaviour of the DCS.
By simulating the actuator signals, the signal behaviour of the actuator controls to
the DCS can be tested, for example, without having to connect the actuator.
Required user level: Specialist (4) or higher.
Diagnostic M0022
Simulation M0023
Actuator signals M0024
Simulation values:
End position OPEN reached.
End position CLOSED reached.
Torque in direction OPEN reached.
Torque in direction CLOSE reached.
Motor protection tripped (thermal fault)
Signification
On time
Number of motor starts/h
Signification
Process setpoint of PID controller
Actual process value of PID controller
Calculated setpoint position for subordinate controller
Signification
FO cable receive level channel 1
The signal assignment for DIN 4 (digital input 4) is incor-
rect.
RS-485 format error of FOC sub-assembly
FO cable baud rate
FO cables FPGA version
Actuator controls
ACV 01.2/ACVExC 01.2