Parameter Group: Torque - Emerson Bettis RTS FQ Series Operating Manual

Fail-safe quarter-turn electric actuator
Table of Contents

Advertisement

Section 8: Parameter Menu
February 2019
CAUTION: NOTE TRAVEL LIMITS
When installing the actuator on an gear or a thrust unit, please take into account the limits
and factors of the gear / thrust unit at parametrization.
CAUTION: SET LIMITS CORRECTLY
When using end limit switch off by torque, the end position limit must be set before
reaching the torque limit. Accordingly, the actuator will only signal the final end position
if the configured torque and the associated end position are reached. If the end position is
not reached, a torque error is reported (see Section 6.2.2)
8.2

Parameter Group: Torque

If no torque was specified with the order, the actuator is supplied from the factory with the
maximum configurable torque.
Table 6.
P2.1
P2.2
P2.3
P2.4
representative for CM03
2)
CAUTION: NOTE GEAR AND THRUST UNITS
When installing the actuator on an additional gear, please take into account the
corresponding values of the gear / thrust unit as you enter the actuator parameters.
To achieve an effective output torque (incl. gear) / output power (including thrust unit)
ratio, the factor gear/thrust unit must be considered.
39
Torque Parameter Group
Sub Menu
Menu Item
Item
Torque
Open
Torque
Close
Torque
Torque limit
Torque
Latching
Poss.
Notes / Comments
Setting
Switch-off torque in OPEN direction
8 - 32Nm
2)
CAUTION: The range can be restricted via menu
item P2.3.
8 - 32Nm
As P2.1, but in CLOSED direction.
2)
Torque to protect the valve, the transmission, or the
thrust unit.
8 - 32Nm
This value limits the setting of parameters P2.1 and
2)
P2.2 to prevent an erroneous increase above the
allowed value of these two parameters.
Off (0)
Unassigned in RTS Compact Multi-Turn CM series
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Parameter Menu