Section 8: Parameter Menu
February 2019
Table 16.
P10.1
4-5
P10.2
P10.3
P10.4
P10.5
P10.6
P10.7
47
Binary Outputs Parameter Group (3)
Menu
Sub Menu
Poss. Setting
Item
Item
47: Pos.=Int2
48: Pos.=Int3
49: Pos.=Int4
50:
Pos.=EmergPos
51: Bus Bit 1
52: Bus Bit 2
53: Bus Bit 3
54: Bus Bit 4
55: Bus Bit 5
56: Bus Bit 6
57: Bus Bit 7
58: Bus Bit 8
Binary
Output 1
59: Virtual 1
Output
60: Virtual 2
61: Virtual 3
62: Virtual 4
63: Line
voltage OK
64: Control
voltage OK
65: Oil pressure
OK
66: Oil level OK The oil level is OK.
67: Pump OK
0: Normal
1: Inverted
Binary
Output
Output
conf. 1
2: Norm.
flashing
3: Inv. flashing
Bin. Output Output 2
see Output 1
Output 2
see Output 1
Bin. Output
conf.
conf.
Bin. Output Output 3
see Output 1
Output 2
see Output 1
Bin. Output
conf.
conf.
Bin. Output Output 4
see Output 1
MAN-02-04-60-0351-EN Rev. 3
Notes / Comments
Position = Intermediate position 2. The width of the
interval is set with the parameter P8.6.
Position = Intermediate position 3. The width of the
interval is set with the parameter P8.6.
Position = Intermediate position 4.The width of the
interval is set with the parameter P8.6.
Position = emergency position. The width of the interval
is set with the parameter P8.6.
In existing bus interface (hardware option) the output is
set according to the selected bit bus.
Configurable output function
Supply voltage for the motor is OK
The auxiliary voltage for the SMARTCON control is
OK. This function is only available if the auxiliary
voltage output is not switched on (P6.5 to 0).
The oil pressure is higher than the minimum
pressure (P6.10).
The temperature sensor in the pump motor and the
external motor protection have not tripped.
Output 1 is set to normal, i.e. if the condition in
point P10.1 is met, Output 1 is set to HIGH (active
HIGH).
If the condition in point P10.1 is met, Output 1 is set
to LOW (active LOW).
If the condition in point P10.1 is met, Output 1
starts blinking (active HIGH).
If the condition in point P10.1 is not met, Output 1
starts blinking (otherwise it is set to HIGH).
User Instructions
4)
Parameter Menu