Parameter Group: Step Mode

Step mode operation can be used to extend the operating time in certain ranges or for the
whole travel; it is available in local, remote and emergency mode.
Step mode operation can be activated individually for the directions OPEN and CLOSED.
Cycle start, cycle end, cycle duration and interval time can be set separately for both
directions. (see Figure 55)
Table 19.
P12.1
P12.2
P12.3
P12.4
P12.5
P12.6
P12.7
P12.8
P12.9
P12.10
P12.11
Parameter Menu
Step Mode Parameter Group
Sub Menu
Menu Item
Item
Step mode
Mode
function
Step mode
Start Open
function
Step mode
End Open
function
Step mode
Runtime Open 0,1 - 60
function
Step mode
Pause time
function
Open
Step mode
Start Closed
function
Step mode
End Closed
function
Step mode
Run time
function
Closed
Step mode
Pause time
function
Step mode
Timebase
function
Step mode
Speed
function
adaptation
Poss.
Notes / Comments
Setting
disabled
Step mode operation is disabled
Step mode operation is enabled in LOCAL, REMOTE
enabled
and EMERGENCY operation
Local only
Step mode mode is only enabled in LOCAL mode
Remote
Step mode mode is only enabled in REMOTE mode
only
Local +
Step mode mode is enabled in REMOTE and
Remote
LOCAL mode
only
In OPEN direction, position in % from which the step
0 - 100%
mode operation should start.
In OPEN direction, position in % of which the step mode
0 - 100%
operation should end.
Runtime in OPEN direction
0,2 - 60
Pause time in OPEN direction
In CLOSED direction, position in % from which the step
0 - 100%
mode operation should start.
In CLOSED direction, position in % of which the step
0 - 100%
mode operation should end.
0,1 - 60
Runtime in Closed direction
0,2 - 60
Pause time in Closed direction
0: Seconds
Time basis for run and pause times
1: Minutes
Speed adaption not activated. Normal step mode
0:
function.
Speed adaption is activated. The speed is reduced
according to the runtime and pause time in the step
mode range. (Example: Running time 1 sec and
pause time 1 sec results in half the speed). If the
1:
minimum speed is undershot, the actuator clocks in
the converted ratio with the minimum speed. The
speed adjustment is only applicable to actuators of
the type CM and AB CSC.
Section 8: Parameter Menu
Febraury 2019
50