Emerson Bettis RTS FQ Series Operating Manual page 54

Fail-safe quarter-turn electric actuator
Table of Contents

Advertisement

Section 8: Parameter Menu
February 2019
Table 18.
P11.1
P11.2
P11.3
P11.4
P11.5
P11.6
P11.7
P11.8
49
Position Output Parameter Group
Sub Menu
Menu item
Item
Position Output
Function 1
Position Output
Start 1 (at 0%)
Position Output
End 1 (at 100%)
Position Output
Calib. 20mA
Analog Output
Function 2
Begin 2 (at
Analog Output
0%)
End 2 (at
Analog Output
100%)
Analog Output
Calib. 20 mA 2
Poss.
Notes / Comments
Setting
0: off
mA output disabled
1: Position mA output corresponds to the actual position value.
2: Pos.
mA output corresponds to the actual position value
Valvencahr.
taking into account the valve characteristic.
mA output corresponds to the actual torque value.
torque = 100% Close: mAoutput = start
3: Torque 1
torque = 0%: mAoutput = center
torque = 100% Open: mAoutput = end
mAoutput corresponds to the actual torque value.
torque = 100% Close: mAoutput = end
4: Torque 2
torque = 0%: mAoutput = start
torque = 100% Open: mAoutput = end
mAoutput corresponds to the actual torque value.
torque = 150% Close: mAoutput = start
5: Torque 3
torque = 0%: mAoutput = center
torque = 150% Open: mAoutput = end
mAoutput corresponds to the actual torque value.
torque = 150% Close: mAoutput = end
6: Torque 4
torque = 0%: mAoutput = start
torque = 150% Open: mAoutput = end
0 - 20,5
mA
mA value for the Closed (0%) position
{4mA}
0 - 20,5
mA
mA-value for the On (100%) position
{20mA}
Calibrating the output position during the setting of
-10% -
this parameter will output a 20mA (100%) signal. Use
+10% see
this parameter to calibrate accurately the 20mA output
Output 1
signal. (e.g., if you measure 19.8 mA at the output, just
add 1% (0.2 mA. . . 1% of 20mA) to the displayed value)
see
Function 1
see Begin
1
see End 1
see Calib.
20 mA 1