Table 15.
P10.1
Parameter Menu
Binary Outputs Parameter Group (2)
Menu
Sub Menu
Poss. Setting
Item
Item
22: Remote
23: Off
24: no function
25: Motor error
26: Always
27: Never
28: Binary Input 1
29: Binary Input 2
30: Binary Input 3
31: Binary Input 4
32: Binary Input 5
33: Torque Open ma.
34: Torque Closed
ma.
35: Ready Remote
Binary
Output 1
36: Ready Local
Output
37: Ready
Local/remote
38: Lock Open
39: Lock Closed
40: Failsafe OK1
41: Failsafe OK2
42: Failsafe OK3
43: Lock
44: Ready/TorqueOK Actuator is ready and no torque switch off
45: Ready/Remote/
TorqueOK
46: Pos.=Int1
Section 8: Parameter Menu
Notes / Comments
Remote operating mode (selctor switch in position
Remote)
Off operating mode (selector switch in the Off position)
no function
The motor temperature sensor has reported an error
Signal is always on
Signal is always off
Forwarding of binary input to output
Forwarding of binary input to output
Forwarding of binary input to output
Forwarding of binary input to output
Forwarding of binary input to output
As Torque OPEN although it will supress (mask) this
signal in the end position upon torque-dependent
switch off.
As Torque CLOSED although it will supress (mask) this
signal in the end position upon torque-dependent
switch off.
Ready and Remote operating mode
Ready and Local operating mode
Ready and Local or Remote mode
Lock OPEN is enabled. OPEN command is internally
queued with the highest priority and will not be
dropped even in the end position
Lock CLOSED is enabled. CLOSED command is internally
queued with the highest priority and will not be
dropped even in the end position
Failsafe OK (only for failsafe actuators)
Failsafe OK and Ready (only for failsafe actuators)
Failsafe OK,Ready and Remote (only for failsafe
actuators)
Lock Open or Lock Closed is enabled.
Actuator is ready for operation in REMOTE mode and no
torque switch off
Position = Intermediate position 1. The width of the
interval is set with the parameter P8.6.
Febraury 2019