Emerson Bettis RTS FQ Series Operating Manual page 41

Fail-safe quarter-turn electric actuator
Table of Contents

Advertisement

User Instructions
MAN-02-04-60-0351-EN Rev. 3
Figure 53
This changes the bottom line of the display from "SAVE?" to "EDIT?" and the parameter
is stored.
7.3.4
Furthermore, certain parameters (end positions, intermediate positions) can be set using
"TEACHIN". Thus, their configuration is greatly simplified.
After selecting the appropriate menu item (for example: End position) and changhing
the input type from "EDIT?" to "SAVE?", move the selector switch (red) to manual mode
and lock it into place. As you do so, the display will show the message "TEACHIN" and the
current position value will be applied continuously to the parameter value. In this mode,
further to manual operation by hand wheel, the actuator can be motor-driven with the
control switch to the desired position (see Section 6.4).
Figure 54
CAUTION: MAX. TORQUE MUST BE ALREADY SET
Please note that, during motor operation, only torque monitoring remains active, as travel
adjustment will happen subsequently. Therefore, please check beforehand whether the
maximum torque has been already set.
After reaching the desired, to-be-defined position, move the selector switch back to the
neutral position. Finally, the parameter value must still be saved by flipping the selector
switch halfway up and letting it snap back to the neutral position (see Figure 42 to Figure 46).
Control Unit
Display (17)
"TEACHIN"
Display (18)
Section 7: Control Unit