Emerson Bettis RTS FQ Series Operating Manual page 48

Fail-safe quarter-turn electric actuator
Table of Contents

Advertisement

Section 8: Parameter Menu
February 2019
Table 12.
P9.1
43
Binary Inputs Parameter Group (1)
Menu Item
Sub Menu Item
Binary Input
Input 1
Poss. Setting
Notes / Comments
0: no function
This input has no function
OPEN command in REMOTE mode (selector switch in position
1: Open
REMOTE).
CLOSED command in REMOTE mode (selector switch in
2: Closed
position REMOTE).
STOP command in REMOTE mode (selector switch in position
3: Stop
REMOTE).
Self-hold for OPEN, i.e., a short pulse is sufficient and the
4: Open Self-hold
actuator moves then into the end position. Use the STOP
command to stop the actuator.
5: Closed Self hold
Self-hold for CLOSED, see OPEN SELF-HOLD
Superimposed run command; run the actuator in direction
6: Emergency
OPEN regardless of whether the selection switch is set to
Open
REMOTE or LOCAL operation
Superimposed run command; run the actuator in direction
7: Emergency
CLOSED regardless of whether the selection switch is set to
Closed
REMOTE or LOCAL
The actuator may be operated only with a switched signal.
8: Release
Both in local and remote operation
The actuator moves towards OPEN if input is active and
9: Open/Closed
towards CLOSED otherwise
The actuator moves towards CLOSED if input is active and
10: Close/Open
towards OPEN otherwise
11: Positioner
Release of the postioner
12: Open inv.
As open but active low
13: Close inv.
As CLOSED but active low
14: Stop inv.
As STOP but active low
15: Open
As Open Self-Hold but active low
Self-Hold.inv
16: Closed
As Closed Self-Hold. but active low
Self-Hold inv
17: Emergency-
As Emergency-Open but active low
Open inv.
18: Emergency-
As Emergency-Closed but active low
Closed inv.
With activated (switched) signal, the actuator is locked for
19: Block
operation also in local mode
20: Contoller lock
Positioner lock
21: Release Local
The actuator may be operated only with a switched signal.
22: Block Local
As Release Local but active low
Trigger lock OPEN (in LOCAL and REMOTE mode). Actuator
moves with the highest priority to OPEN; command
23: Lock Open
continues internally active after reaching the end position
OPEN. Dropping only with LOCK OFF, Supply OFF or operating
mode OFF.
Trigger lock CLOSED (in LOCAL and REMOTE
mode). Actuator moves with the highest priority to
CLOSED; command continues internally active
24: Lock Closed
after reaching the end position CLOSED. Dropping
only with LOCK OFF, Supply OFF or operating
mode OFF.
25: Lock Off
Drop the lock
Trigger the failsafe function in all operating modes
26: Failsafe
(only functional in Failsafe actuators).
27: Failsafe inv.
As Failsafe, but active low
28: Lock Open inv.
As Lock Open, but active low
29: Lock Closed inv.
As Lock Closed, but active low
30: Lock Off inv.
As Lock Off, but active low
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Parameter Menu