Parameter access response time

The parameters of AnyWireASLINK provide monitoring information of slave modules or the entire system and setting
information of the slave modules.
Parameter data is synchronized between the buffer memory of the RJ51AW12AL and slave modules at a cycle different from
that of the I/O data.
Use the following calculation formulas to obtain the parameter access response time.
Item
Update interval time of an automatically updated parameter
Time required for reading parameters
Time required for writing parameters
*1 The parameters to be accessed are the status details and the sensing level.
*2 The number of target IDs is as follows.
During parameter access: 1
During parameter batch read: The number of IDs registered at the time of automatic address detection
During parameter batch write: The number of IDs registered at the time of automatic address detection
APPX
122
Appendix 4 Processing Time
Calculation formula
*1
Number of AnyWireASLINK connection IDs  Transmission cycle time  3
Number of target IDs  Transmission cycle time  27
Number of target IDs  Transmission cycle time  39
*2
*2