Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 32

Master module
Table of Contents

Advertisement

How to recover from the parameter access error status
For recovery from the parameter access error status, refer to the following.
Page 80 List of Error Codes
To recover from the parameter access error status, eliminate the error cause, and power off and on the AnyWireASLINK
system or turn off and on 'Error flag clear command' (Y0).
Status after recovery
After recovery from parameter access error status, the following status is resulted:
Error description
Slave module hardware error
*1
Parameter value error
Slave module status error
*1
Same ID used error
*1
No ID setting error
Parameter access error
Parameter access target module ID error
Type mismatch error
Replacement error due to use of slave module
of earlier device version
New ID error
*1 When factors causing errors are eliminated, the data in 'Number of the alarm IDs' (Un\G9984) and 'Alarm ID information storage area'
(Un\G9985 to Un\G10112) are cleared.
1 FUNCTIONS
30
1.9 Parameter Access Error Detection Function
Signal status
• 'Slave module alarm signal' (X10) turns off.
• The data in 'Latest error code storage area' (Un\G10256) is cleared.
• The data in 'Latest error ID storage area' (Un\G10257) is cleared.
• The data in 'Number of the alarm IDs' (Un\G9984) is cleared.
• The data in 'Alarm ID information storage area' (Un\G9985 to Un\G10112) is cleared.
• 'Parameter access error' (X12) turns off.
• The data in 'Latest error code storage area' (Un\G10256) is cleared.
• The data in 'Latest error ID storage area' (Un\G10257) is cleared.
• The data in 'Number of the error IDs' (Un\G8192) is cleared.
• The data in 'Error ID information storage area' (Un\G8193 to Un\G8320) is cleared.
• The data in 'Error ID information bit area (bit output)' (Un\G8704 to Un\G8719) is cleared.
• The data in 'Error ID information bit area (bit input)' (Un\G8736 to Un\G8751) is cleared.
• The data in 'Error ID information bit area (word output)' (Un\G8768 to Un\G8799) is cleared.
• The data in 'Error ID information bit area (word input)' (Un\G8800 to Un\G8831) is cleared.
• 'Slave module alarm signal' (X10) turns off.
• The data in 'Latest error code storage area' (Un\G10256) is cleared.
• The data in 'Latest error ID storage area' (Un\G10257) is cleared.