Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 85

Master module
Table of Contents

Advertisement

Error code
Error details and causes
3064H to 3066H
RJ51AW12AL hardware failure
3068H
CPU module stop error (IORSTL
signal detection)
3069H
System error (NMI signal detection)
306BH
CPU module error (ITERR signal
detection)
306CH
ASIC access error (library I/F function
access error)
Action
A malfunction has been detected in the RJ51AW12AL
hardware.
Reset the CPU module or power off and on the system.
If the error occurs again, the RJ51AW12AL may be in failure.
Please consult your local Mitsubishi representative.
A stop error has occurred in the CPU module.
Check the error in the "Module Diagnostics" window of an
engineering tool and correct the error.
An internal control power supply error or watchdog timer error
has occurred.
Check the error in the "Module Diagnostics" window of an
engineering tool and correct the error.
The RJ51AW12AL cannot receive signals from the CPU
module.
Check the error in the "Module Diagnostics" window of an
engineering tool and correct the error.
A malfunction (ASIC access error) has been detected in the
RJ51AW12AL hardware.
Reset the CPU module or power off and on the system.
If the error occurs again, the RJ51AW12AL may be in failure.
Please consult your local Mitsubishi representative.
Detailed information
4 TROUBLESHOOTING
4.4 List of Error Codes
4
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r seriesMelsec iq anywireaslink rj51aw12al

Table of Contents