Error Status Automatic Recovery Function - Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual

Master module
Table of Contents

Advertisement

1.10

Error Status Automatic Recovery Function

This function allows for automatic error reset for DP/DN disconnection errors and parameter access errors after the error
status is cleared.
If this function is not used, it is necessary to eliminate the error cause, and power off and on the AnyWireASLINK system or
turn on and off 'Error flag clear command' (Y0).
Error that can be automatically recovered
The following shows the errors that can be automatically recovered.
Error code
Error description
0CCAH
DP/DN disconnection
error
0D30H
Parameter access error
*1 The error causes must be eliminated from all the slave modules in which errors have occurred.
*2 If the errors 0CCAH and 0D30H have occurred in one slave module, the causes of both the errors must be eliminated.
Setting method
Set the error status automatic recovery function in "Error status automatic recovery" of "Basic setting". ( Page 50 Error
status automatic recovery setting)
Status when an error occurred
• 'DP/DN disconnection error' (X4) turns on.
• Error ID information is registered in the buffer
memory address. ( Page 26 How to check the
transmission cable disconnection status)
• 'Parameter access error' (X12) turns on.
• Error ID information is registered in the buffer
memory address. ( Page 29 How to check the
parameter access error status)
Status when an error is cleared
• 'DP/DN disconnection error' (X4) turns off.
• The error ID information registered in the buffer
memory address is cleared. (corresponding ID
*2
only)
• 'Parameter access error' (X12) turns off.
• The error ID information registered in the buffer
memory address is cleared. (corresponding ID
*2
only)
1.10 Error Status Automatic Recovery Function
1
*1
*1
1 FUNCTIONS
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r seriesMelsec iq anywireaslink rj51aw12al

Table of Contents