Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 106

Master module
Table of Contents

Advertisement

Parameter access setting
■Parameter access setting (Un\G10320)
Specify the parameter access method. When a value other than those below is stored, the parameter is read.
• 0000H: Read (slave module  RJ51AW12AL  CPU module)
• 0001H: Write (CPU module  RJ51AW12AL  slave module)
• 0002H: Remote address change (CPU module  RJ51AW12AL  slave module)
However, when the output signals below are executed, the set value is ignored.
• 'Parameter batch read command for the slave module' (Y11)
• 'Parameter batch write command for the slave module' (Y12)
Parameter access target module ID specification
■Parameter access target module ID specification (Un\G10321)
Specify the access ID for accessing the parameters of individual IDs.
Write one of the following to specify the ID.
• 0000H to 00FEH: ID of a bit output slave module
• 0200H to 02FEH: ID of a bit input slave module or bit I/O combined slave module
• 0400H to 05FEH: ID of a word output slave module
• 0600H to 07FEH: ID of a word input slave module or word I/O combined slave module
However, when the output signals below are executed, the set value is ignored.
• 'Parameter batch read command for the slave module' (Y11)
• 'Parameter batch write command for the slave module' (Y12)
Change ID specification
■Change ID specification (Un\G10323)
Specify a new ID (address) with the remote address change function.
Write one of the following to specify the ID.
• 0000H to 00FEH: ID of a bit output slave module
• 0200H to 02FEH: ID of a bit input slave module or bit I/O combined slave module
• 0400H to 05FEH: ID of a word output slave module
• 0600H to 07FEH: ID of a word input slave module or word I/O combined slave module
However, when the output signals below are executed, the set value is ignored.
• 'Parameter batch read command for the slave module' (Y11)
• 'Parameter batch write command for the slave module' (Y12)