Address and ID
The following table shows the relationship between address and ID.
Model
Bit type
Output slave module
Input slave module
I/O combined slave module
Word type
Output slave module
Input slave module
I/O combined slave module
When data is written to the slave module, the data is written in the range of the above address (not in the range of the ID).
■Slave module that uses both bit transmission and word transmission
The following table shows the address and ID of the slave module that uses both bit transmission and word transmission.
Item
Description
Address
Use word address on slave modules that use both bit transmission and word transmission.
When a word address is set, the same address will be applied to the bit address.
For example, when the word address is set to 120, the bit address is set to 120.
ID
ID is assigned as a word address.
For example, when address 120 (0078H) is set on the word input slave module, the ID is set to 0678H.
*1 Slave modules for which bit address is selected do not perform word transmission. For the operation of slave modules for which bit
address is selected, refer to the following.
 Manual of the slave module used (manufactured by Anywire Corporation)
Address setting example
■Assignment by 2-point bit slave module only
When 0 is set for the input slave module address, and 0 and 2 for the output slave module address, bits are occupied as
follows.
• Buffer memory address of the input slave module
Buffer memory address
Bit No.
15
Un\G0
15
Areas occupied by address 0 of the 2-point slave module: Un\G0.0, Un\G0.1
• Buffer memory address of the output slave module
Buffer memory address
Bit No.
15
Un\G4096
15
Areas occupied by address 0 of the 2-point slave module: Un\G4096.0, Un\G4096.1
Areas occupied by address 2 of the 2-point slave module: Un\G4096.2, Un\G4096.3
Address
0 to 254
0 to 510
14
13
12
11
10
14
13
12
11
10
14
13
12
11
10
14
13
12
11
10
ID
0000H to 00FEH
0200H to 02FEH
0400H to 05FEH
0600H to 07FEH
*1
9
8
7
6
5
9
8
7
6
5
9
8
7
6
5
9
8
7
6
5
2.5 Slave Module Address Setting
4
3
2
1
0
4
3
2
1
0
4
3
2
1
0
4
3
2
1
0
2 PARAMETER SETTINGS