Installation Guide
Resolution of analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
5.3.7 Control Card, 24 V DC Output
Terminal number
Output voltage
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
5.3.8 Control Card, +10 V DC Output
Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

5.3.9 Control Card, RS485 Serial Communication

Terminal number
Terminal number 61
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).

5.3.10 Control Card, USB Serial Communication

USB standard
USB plug
Connection to the PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to the
USB connector on the drive.

5.3.11 Relay Outputs

Programmable relay outputs
Relay 01 terminal number
Maximum terminal load (AC-1)
load)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
load)
Maximum terminal load (DC-13)
Relay 02 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
cosφ 0.4)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
cosφ 0.4)
Danfoss A/S © 2021.05
on 1–3 (NC), 1–2 (NO) (resistive
(1)
(inductive load @ cosφ 0.4)
(1)
on 1–2 (NO), 1–3 (NC) (resistive
(1)
(inductive load)
(1)
on 4–5 (NO) (resistive load)
(1)
on 4–5 (NO) (inductive load @
(1)
on 4–5 (NO) (resistive load)
(1)
on 4–5 (NO) (inductive load)
(1)
on 4–6 (NC) (resistive load)
(1)
on 4–6 (NC) (inductive load @
(1)
()()
Specifications
24 V +1, -3 V
10.5 V ±0.5 V
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
1.1 (full speed)
USB type B plug
1–3 (break), 1–2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
60 V DC, 1 A
24 V DC, 0.1 A
4–6 (break), 4–5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
AN354546796134en-000201 / 130R0954 | 33
12 bit
12, 13
200 mA
50
15 mA
2