Usage Setting local interface and TCP port to listen to.
Acceptable port range is in range <1-65335> (default port 502). Omitting
the "port" argument leaves the port number unchanged.
Use "no listen" to reset the setting to default (listen on any interface, port
502)
Use "show listen" to show the current listen setting.
The setting is only applicable when configuring the Modbus Gateway in
"server" mode (see
Default values Any interface, port 502 ("listen iface any port 502")
41.2.7 Setting ASCII Timeout
Syntax [no] ascii-timeout <MILLISECONDS>
Context
Modbus Gateway Configuration
Usage Set ASCII Timeout, i.e., the maximum time between two frames in ASCII
mode. Allowed range is <10-7050> (milliseconds).
Use "no ascii-timeout" to reset the timeout to the default value (1000
milliseconds).
Use "show ascii-timeout" to show the current timeout setting.
The "ascii-timeout" command is only applicable when configuring the
Modbus Gateway to use "ascii" as serial protocol (see
Default values 1000
41.2.8 Setting RTU Interval
Syntax [no] rtu-interval <MILLISECONDS>
Context
Modbus Gateway Configuration
Usage Set RTU Interval, i.e., the minimum time between two frames in RTU
mode. Allowed range is <10-7050> (milliseconds).
Use "no rtu-interval" to reset the interval to the default value (50 mil-
liseconds).