Example of flue gas tem-
perature sensor
Example of common main-
tained boiler return tem-
perature
Maximum plant size
Building Technologies
HVAC Products
Main menu > Commissioning > Extra configuration > Boiler 1 > Inputs
Operating line
Flue gas temperature sensor
* Here, the free inputs are available
The inputs on the basic module are designated RMK770.Xn, those on the extension
modules RMZ...Xn. If 2 identical extension modules are used, they will be called
RMZ789(1) and RMZ789(2).
After the assignment, following appears: "Flue gas temperature sensor N.X4" (N= short
designation of basic module RMK770).
By assigning input terminal RMK770.X4, the flue gas temperature sensor is activated.
For other settings, refer to chapter 7 "Boiler temperature control".
Assignments made or preconfigured assignments can be removed again by using set-
ting --- (none).
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Outputs
Operating line
Maint boiler return temp 3-pos
* Here, the free outputs are available for selection
Available for selection are the free terminal pairs (Q1/Q2, Q3/Q4, Q5/Q6) for the on and
off signal (refer to subsection 3.3.2 "Terminal assignment and properties of outputs").
Refer to subsection 3.3.4 "Maximum configuration".
3.4.1
Hydraulics-dependent inputs and outputs of function
block "Boiler sequence manager"
TFg
TFg
T
TBo
T
T
BuMdltUp
BuSt1
BuMdltDn
BuSt2
TRtBo
T
BoPu_B
BoPu_A
VlvRtMx
The sensors and actuating devices in the highlighted part belong to function block
"Boiler sequence manager".
By making an assignment to an input or output terminal, the relevant plant components
will be activated.
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs
Operating line
Main flow sensor
Main return sensor
MBRT return sensor
Consumer return sensor
* Here, the free inputs are available for selection
** These sensors are automatically configured when selecting the plant type (exception: Basic type K)
Boiler Sequence Controller RMK770
3 Commissioning
Range
RMK770..., RMZ7...*
Range
RMK770..., RMZ7...*
Boiler sequence management
MnPu_A
TBo
T
MnPu_B
BuMnSt
TRtBo
T
BoPu
TRtMx
VlvShOff
T
MnVlvRtMx
Range
RMK770..., RMZ7...*
Factory setting
---
Factory setting
---
PrCtrVlvMx
T
TRtPrCtr
TMnFl
T
TRtCo
TRtMn
T
T
Name
TMnFl**
TMnRt**
TRtMx
TRtCo
TFlPrCtr
TPu_A
T
TPu_B
T
37/226