Reset Function; What Is The Reset Function; No Communication Notification Function - Panasonic FP2 ET-LAN Technical Manual

Table of Contents

Advertisement

13.3 Reset Function

13.3.1 What is the Reset Function?

The reset function is used to restart only the ET-LAN unit without cutting off the power supply for the
system.
Using the reset function enables the ET-LAN unit to be the operable state when an unrecoverable error
has occurred in the ET-LAN unit.
Also, using the reset function periodically when the ET-LAN unit is not communicating may help to
prevent an accidental communication error.
The no communication notification function is available which is useful to detect the time to execute the
reset function.

13.3.2 No Communication Notification Function

The no communication notification function is a function to notify that communication is not performed
longer than a specified time for the connection opened by the open processing of the ET-LAN unit.
Using the no communication notification function enables to detect the state that the ET-LAN unit is not
communicating.
Use this function when executing the reset function.
Procedure
1. Write a value in the following address of the initial information setting area (Shared memory Bank 0) to
execute the initial processing.
Initial information setting area (Bank 0)
Address
Name
No communication
208H
connection time type
No communication
209H
connection detection
timer value
2. When communication is not performed for the period of the specified time-out value, the flags of the
bits corresponding to each connection in the following handshake area (Shared memory Bank 0) turn on.
Handshake area
Expanded complete request area 2 (Bank 0)
Address
366H
13-8
Default
Setting value/Explanation
Set the base time for the no communication connection detection
timer value.
0000H
0000H : × 2 minutes
Other than 0000H : x 6 seconds
Setting time = [Setting value (1 - FFFFH)] × [Base time]
- Set the time to detect a no-communication state after connection
establishment.
0000H
- The setting value of the above 208H is used as the base time.
- When the setting value is larger than 0064H,
in case of x 2 minutes : 200 minutes
in case of x 6 seconds : 10 minutes
BIT
Description of signal
bit8
No communication time-out signal (Connection 1)
bit9
No communication time-out signal (Connection 2)
bitA
No communication time-out signal (Connection 3)
bitB
No communication time-out signal (Connection 4)
bitC
No communication time-out signal (Connection 5)
bitD
No communication time-out signal (Connection 6)
bitE
No communication time-out signal (Connection 7)
bitF
No communication time-out signal (Connection 8)

Hide quick links: