Panasonic FP2 ET-LAN Technical Manual page 192

Table of Contents

Advertisement

- Time chart for reading e-mail error log
- Procedure to read e-mail error logs
(1) The e-mail error log notified request signal is turned ON.
- The address 36AH (bit 5) in the e-mail request signal area (Bank: 0) is turned ON.
(2) The e-mail error log is transferred to the shared memory.
(3) Confirm that the e-mail error log complete signal (Bank: 0) is ON.
- Confirm that the address 362H (bit 5) in the e-mail complete signal area (Bank: 0) is ON.
(4) The e-mail error log area (Bank: 10H, Addresses: from 200H) in the e-mail error log area of the
shared memory is read.
(5) The e-mail error log request signal is turned OFF.
(6) The e-mail error log complete signal is turned OFF. To read the next error log, be sure to confirm that
this e-mail error log notified complete signal has been OFF.
Reference: <Chapter 4 Confirming the Design Contents>
11-24