PLC application error
Error
Error name
code
60H
Parameter error
61H
Data error
62H
Registration error
63H
Mode error
65H
Protect error
66H
Address error
67H
No data error
72H
Time-out error
73H
Time-out error
74H
Time-out error
Steps to take
When using the computer link function:
The code used is for an area specification parameter that does not exist, or is a
code that cannot be used with that command (X, Y, D, etc.). An inappropriate
code is being used for the function specification parameter (0, 1, 2, etc.).
Steps to take:
Specify using the correct format code.
When using the computer link function:
An error occurred indicating that the specification for the contact number, area
number, or the code format used to handle the data (BCD, HEX, etc.) is
excessive, insufficient, or the wrong range has been specified.
When using the data transfer function:
The wrong field has been specified for the source node or another node.
Steps to take:
Specify using the correct format code.
When using the computer link function:
Too many registrations have been entered, or a registration has not been entered
(monitor registration, trace registration, etc.). When there are too many
registrations, reset the registrations.
Steps to take:
Specify using the correct format code.
When using the computer link function:
When a command was transmitted, the operation mode was one in which that
command cannot be processed.
Steps to take:
Specify using the correct format code.
When using the computer link function:
An attempt was made to write data to a program area or system register while the
memory protect status was in effect.
Steps to take:
Data cannot be written while the memory protect status is in effect.
When using the computer link function:
An error occurred indicating that the code format (BCD, HEX, etc.) for the
address (program address, absolute address, etc.) data is excessive, insufficient,
or the wrong range has been specified.
Steps to take:
Specify using the correct format code.
When using the computer link function:
The data to be read does not exist. (An attempt was made to read a comment
registration or other data that has not been written.)
Steps to take:
Specify using the correct format code.
When using the data transfer function:
Timeout error occurred while waiting for a transmission answer
Steps to take:
Use the application program to send the transmission again.
When using the data transfer function:
Timeout error occurred while waiting for the transmission buffer to become empty
Steps to take:
Use the application program to send the transmission again.
When using the data transfer function:
Timeout error occurred while waiting for a response
Steps to take:
Use the application program to send the transmission again.