Panasonic FP2 ET-LAN Technical Manual page 154

Table of Contents

Advertisement

Case 1
When the auto connection function is not used: Setting is performed only using the ladder
program.
The following settings are required using the ladder program.
Setting item
Internal relay allocation
Initialization processing
Open processing
Data transfer
- Setting using the ladder program
Internal relay allocation
Classification
Completed signal area
Request signal area
Data register allocation
Classification of
processing
Initialization
processing
Open processing
Data transfer
processing
Data transfer area
10-12
Setting method
Ladder program
Ladder program
Ladder program
Ladder program
Device number
R0 to R1F
R40 to R5F
Device
Setting item
number
DT10 to
Source node IP address
DT11
DT12
Communication function setting
between networks
DT13
Source node MEWTOCOL
station No.
DT20
Open method
DT21
Source node port No.
DT22 to
Destination node IP address
DT23
DT24
Destination node port No.
DT25
Destination node MEWTOCOL
station No.
DT22 to
Source node route No.
DT23
Destination node MEWTOCOL
station No
Number of transferred words
DT100 to
Transfer data writing area
DT102
Device used in program example
RC: Initialization complete signal
RD: Initialization error signal
R11: Open error signal (Connection 1)
R4C: Initialization request signal
R50: Open request signal (Connection 1)
Settings used in the program
192.168.1.1
(C0A80101H)
Not used
01
MEWTOCOL communication
TCP/IP: Full Passive open
8000
192.168.1.2
(C0A80102H)
8000
05
1
05
3