Notes:
1. Utility Interconnection Voltage and Frequency Trip Limits and Trip
Times:
Condition
Simulated utility source
Voltage (V)
A
< 0.50 Vnor
B
0.50 Vnor ≤ V < 0.88 Vnor
(Adjustable Set Points)
C
1.10 Vnor < V < 1.11 Vnor
(Adjustable Set Points)
D
1.20 Vnor ≤ V
E
Rated
F
Rated
G
Rated
2. Utility interactive evaluations were conducted with the following
firmware:
15 kW.
DSP Firmware versions (208V):
0x1DF3
MICRO Firmware versions (208V): NA
DSP Firmware versions (480V):
0xB734
MICRO Firmware versions (480V): NA
25 kW.
DSP Firmware versions (208V):
0x59OA
MICRO Firmware versions (208V): NA
DSP Firmware versions (480V):
MICRO Firmware versions (480V): NA
3. Surge Testing for Combination Wave (1.2/50us) was done at 6
kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100kHz)
was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were
performed using both polarities, for common mode and differential mode
coupling, 20 pulses each test. After surge testing the unit was operational
with control functionally verified by frequency and voltage disconnect
tests.
Installation and Operation Manual
INGECON®SUN SMART U
Maximum time (sec) at 60 Hz
before cessation of current to the
Frequency (Hz)
simulated utility
Rated
0.16
Rated
0.16 to 2.667 (Adjustable Set
Points)
Rated
0.16 to 2 (Adjustable Set Points)
Rated
0.16
f > 60.5
0.16
f < (59.8 – 57.0)
0.16 to 300
(Adjustable Set
Points)
f < 57
0.16
AAS1038
Check sums:
Check sums: NA
AAS1037
Check sums:
Check sums: NA
AAS1036
Check sums:
Check sums: NA
AAS1035
Check sums: 0x2981
Check sums: NA
AAS2000IKI05
AAS2000IKI05
Rev. _
Date: February 2011