Ingeteam Ingecon Sun Smart U Installation And Operation Manual page 19

Table of Contents

Advertisement

Installation and Operation Manual
INGECON®SUN SMART U
AAS2000IKI05
AAS2000IKI05
Rev. _
Date: February 2011
Ac Output
Ingecon®Sun
Output power factor rating
Operating voltage range
(ac) (L-L)1
Operating frequency range
Number of phases
Nominal output voltage (ac)
Normal output frequency
Maximum continuous
output current ac per line
Power
Maximum output fault
current (ac) and duration
Maximum output
overcurrent protection
Utility interconnection
voltage and frequency
trip limits and trip time
accuracy.
Voltage:
Trip limit
Frequency:
and trip time
accuracy
Time
Normal operation
temperature range
Maximum full power
operating ambient
Enclosure Rating Type
15U 208
15U 480
>0.99
183 - 229
422.5 - 528
V ac
V ac
59.3 - 60.5 Hz
3F + N
208 V
480 V
60 Hz
41.6
18
15 kVA
15 kVA
(15 kW)
(15 kW)
159A @
74A @ 9ms
9.6ms
70 A
30 A
+/-1%
+/-0.1 Hz
0.060 secs
-15 - +55°C
+55°C
3R
25U 208
25U 480
183 - 229
422.5 - 528
V ac
V ac
208 V
480 V
69.4A
30.1 A
25 kVA
25 kVA
(25 kW)
(25 kW)
206A @
266A @
11.2ms
8.8ms
100 A
50 A
+45°C
Page 19