Installation and Operation Manual
INGECON®SUN SMART U
AAS2000IKI05
DC terminal
strip 1
AAS2000IKI05
Rev. _
Date: February 2011
INGECON SUN 15 U 208V and INGECON SUN 15 U 480V with multi
input.
This units are equiped with a terminal strip of 10 connectors for each pole
for wires with a maximum section AWG 6. Wires have to be equiped with
insulated terminals.
This option has to be required when equipments are ordered. Pole that
installer intend to ground has to be indicated. Positive pole and negative
pole will connect to DC terminal strip 1 or DC terminal strip 2 depending
on the pole that has been grounded:
- When positive pole is grounded, positive pole is connected in DC terminal
strip 2, and negative pole to DC terminal strip 1.
- When negative pole is grounded, positive pole is connected in DC termi-
nal strip 1, and negative pole to DC terminal strip 2.
DC terminal
strip 2
Page 47