Date: February - Ingeteam Ingecon Sun Smart U Installation And Operation Manual

Table of Contents

Advertisement

AC Terminals Ingecon Sun 25U 480. Use 194ºF (90ºC) wire, either 10/AWG
copper or 8/AWG aluminium:
- Copper wires:
- Aluminium wires:
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
DC Terminals Ingecon Sun 25U 208 and Ingecon Sun 25U 480.Use 194ºF
(90ºC) wire, either 4/AWG copper or 2/AWG aluminium:
- Copper wires:
- Aluminium wires:
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
Tightening torques
AC Terminals Ingecon Sun 15U 208:
- Copper wires 8/AWG:
- Aluminium wires 6/AWG:
AC Terminals Ingecon Sun 15U 480:
- Copper wires 12/AWG:
- Aluminium wires 12/AWG:
DC Terminals Ingecon Sun 15U 208 and Ingecon Sun 15U 480:
- Copper wires 8/AWG:
- Aluminium wires 6/AWG:
AC Terminals Ingecon Sun 25U 208:
- Copper wires 6 AWG:
- Aluminium wires 4/AWG:
AC Terminals Ingecon Sun 25U 480:
- Copper wires 10/AWG:
- Aluminium wires 8/AWG:
DC Terminals Ingecon Sun 25U 208 and Ingecon Sun 25U 480:
- Copper wires 4/AWG:
- Aluminium wires 2/AWG:
Page 8
Minimun 10/AWG 0.008in²
Minimun 8/AWG 0.012in²
Minimun 4/AWG 0.032in²
Minimun 2/AWG 0.052in²
8.5 pound-in (9 Nm).
12.4 pound-in (18.6 Nm).
8.5 pound-in (9 Nm).
8.5 pound-in (9 Nm).
8.5 pound-in (9 Nm).
12.4 pound-in (18.6 Nm).
12.4 pound-in (18.6 Nm).
12.4 pound-in (18.6 Nm).
8.5 pound-in (9 Nm).
8.5 pound-in (9 Nm).
12.4 pound-in (18.6 Nm).
16.9 pound-in (31.3 Nm).
Installation and Operation Manual
INGECON®SUN SMART U
AAS2000IKI05
AAS2000IKI05

Date: February 2011

Rev. _

Advertisement

Table of Contents
loading

Table of Contents