I/O Communication - Output Setting
D
8
Select this check box if the controller CPU will not exchange output data with the EtherNet/IP network.
For example, when replacing the adaptor, select this check box and you can replace the adaptor without turn-
ing OFF the power supply and without any errors occurring. Clear the check box after replacing the adaptor
and that adaptor will exchange input data normally.
Instance No. [OUT]
9
Set the same number as Instance No. [IN] of the other device.
Refer to 4.2.3 ( 1 ) Details of the Connection List Tab Page on page 4-8 for more information.
Output Register
10
Set the leading address of the OW registers of the machine controller.
Set the leading address to a unique value in the range displayed at the top right of the Connection List tab page.
Size (Byte)
11
Set the same size as Input Size [Byte] of the other device. The setting range is 1 to 500 bytes.
5.2 Using the 263IF-01 as an Adaptor
5.2.2 Examples of EtherNet/IP Transmission Definition Settings
5-19