Run/Idle Header
5
Description
The following table gives the structure of the string to the left of "$ connection parameters" in the EDS file.
Item
Input Data (Target → Originator)
Bit No.
15
• Bit 15 to bit 12 = 4 (hexadecimal)
Run/Idle Header: Input data is valid (check box is
How to
selected)
Check the
Setting
• Bit 15 to bit 12
Content
Run/Idle Header: Input data is invalid (check box
is cleared)
Specific Example
[Connection Manager]
Connection1 =
0x04010002,
0x11640405,
Look here, and set Run/Idle Header.
Item
Input Data (Target → Originator)
Hexadecimal
Notation
Bit No.
15
Since bit 15 to bit 12 ≠ 4 (hexadecimal), invalidate (clear the check box of) Run/Idle Header: Input Data (Target
→ Originator).
Since bit 11 to bit 8 = 4 (hexadecimal), validate (select the check box of) Run/Idle Header: Output Data (Origina-
tor → Target).
5.1.2 Examples of EtherNet/IP Transmission Definition Settings
Run/Idle Header:
14
13
12
4 (hexadecimal)
$ trigger & transport
$ connection parameters
Run/Idle Header:
0
14
13
12
5.1 Using the 263IF-01 as a Scanner
Run/Idle Header:
Output Data (Originator → Target)
11
10
9
• Bit 11 to bit 8 = 4 (hexadecimal)
Run/Idle Header: Output data is valid (check box is
selected)
• Bit 11 to bit 8
4 (hexadecimal)
Run/Idle Header: Output data is invalid (check box
is cleared)
Run/Idle Header:
Output Data (Originator → Target)
4
11
10
8
9
8