5.1 Using the 263IF-01 as a Scanner
5.1.2 Examples of EtherNet/IP Transmission Definition Settings
Configuration Instance No.
4
Description
Check the content set for the configuration instance number based on the information on the last line of "Connec-
tion" under the [Connection Manager] section in the EDS file.
Has "24"
"24" is missing
Specific Example 1
The minimum is 1 and the
maximum is 199, so the desired
value between 1 and 199 is
Configuration Instance No.
 In the actual EDS file, the [Params] section comes before the [Connection Manager] section.
Specific Example 2
[Connection Manager]
5-14
String Elemental
Right of "24" is "[Param
Right of "24" is numeric value
[Connection Manager]
[Params]
Connection1 =
0x04010002,
"20 04 24 01 2C [Param3] 2C [Param4]";
24, so look to the right.
Configuration Instance No. is 1.
Numeric value within the range of "$min,max" in the corresponding
]"
"[Param
]" section in the EDS file.
2-digit numeric value to the right of "24"
Same numeric value as the value set for Input Setting: Instance No.
[IN] or Output Setting: Instance No. [OUT] on the Connection List
tab page
Connection1 =
0x04010002,
"20 04 24 [Param22] 2C [Param3] 2C [Param4]";
24, so look to the right.
Configuration Instance No. references
Param22.
Param22 =
0,
,,
0x0000,
0xC6,
1,
"Configration Instance No.",
"Ignored Path",
"",
1,199,1,
,,,,
,,,,
;
$ trigger & transport
Description
$ trigger & transport
$ reserved, shall equal 0
$ path size, path
$ descriptor
$ data type : UINT
$ data size in bytes
$ units
$ help string
$ min, max, default data values
$ mult, dev, base, offset scaling
$ mult, dev, base, offset link
$ decimal places